Apparent power → current

kVA to Amps Calculator

Convert kilovolt-amps (kVA) to amps (A) for single-phase and three-phase power, at any voltage — the same calculation used to size generators, transformers and breakers.

Instant results No sign-up Free
kVA → Amps Converter
V
Current draw
144.34 A
100 kVA × 1000 ÷ (√3 × 400 V) = 144.34 A

Balanced three-phase load, line-to-line voltage. Change any value and the result updates instantly.

1 kVA at 240V, single-phase= 4.17 A
10 kVA at 400V, three-phase= 14.43 A
100 kVA at 480V, three-phase= 120.28 A
500 kVA at 400V, three-phase= 721.69 A

The kVA to amps formulas

Current follows directly from apparent power and voltage. Single-phase divides by the voltage once; three-phase also accounts for the power being shared across three conductors. The three-phase kVA to amps calculator adds a line-to-neutral mode for systems specified that way.

Single-phase
I = (kVA × 1000) ÷ V

For one live conductor — homes, small appliances, single-phase generators and UPS units.

Three-phase · line-to-line
I = (kVA × 1000) ÷ (√3 × V)

The standard three-phase formula, using the line-to-line voltage (400V, 480V) found on most nameplates.

Three-phase · line-to-neutral
I = (kVA × 1000) ÷ (3 × V)

Used when the voltage given is line-to-neutral (for example 230V in a 400V system) instead of line-to-line.

Why there is no power factor in this formula

Power factor converts kVA into kW — it separates apparent power from real power. Current is not part of that step: once you know the apparent power (kVA) and the voltage, the current follows on its own. Carry the same load through kVA → kW → amps and the power factor cancels out exactly, which is the proof it never belonged here.

If a calculator asks for power factor to turn kVA into amps, it is silently answering the kW question instead — and its result will be too high by exactly that factor. This site never asks for one. The full derivation is on the methodology page.

Quick answers

The conversions people look up most, answered outright. Every figure below comes from the same formulas as the calculator — nothing is rounded from a neighbouring value.

1 kVA to amps: 4.17 A at 240V single-phase · 1.44 A at 400V three-phase
5 kVA to amps: 20.83 A at 240V single-phase · 7.22 A at 400V three-phase
10 kVA to amps: 41.67 A at 240V single-phase · 12.03 A at 480V three-phase
15 kVA to amps: 21.65 A at 400V three-phase · 18.04 A at 480V three-phase
25 kVA to amps: 104.17 A at 240V single-phase · 36.08 A at 400V three-phase
50 kVA to amps: 72.17 A at 400V three-phase · 60.14 A at 480V three-phase
100 kVA to amps: 144.34 A at 400V three-phase · 120.28 A at 480V three-phase
500 kVA to amps: 721.69 A at 400V three-phase · 601.41 A at 480V three-phase

kVA to amps conversion chart

The most common ratings at the three voltages electricians ask about most. The full kVA to amps chart covers every standard rating from 0.5 to 3,000 kVA at 120, 208, 240, 400 and 480 volts.

kVA240V · single-phase400V · three-phase480V · three-phase
14.17 A1.44 A1.20 A
520.83 A7.22 A6.01 A
1041.67 A14.43 A12.03 A
25104.17 A36.08 A30.07 A
50208.33 A72.17 A60.14 A
100416.67 A144.34 A120.28 A
2501,041.67 A360.84 A300.70 A
5002,083.33 A721.69 A601.41 A

Related calculators

Every conversion in the kVA sizing job, each with its own worked examples and charts. If you are starting from a measured or nameplate current instead, the amps to kVA calculator runs the same math backwards. Generator work has its own generator kVA to amps calculator with standard genset sizes loaded, and transformer nameplates are covered by the transformer kVA to amps calculator, which reads both sides of the unit at once.

Worked examples

Three everyday jobs, done step by step with the same formulas the calculator uses.

Transformer · 480V three-phase

A 75 kVA transformer on a 480V three-phase supply: 75,000 ÷ (√3 × 480) = 75,000 ÷ 831.38 — so its full-load current is 90.21 A per phase. That is the figure you size the breaker and feeder cable against. The transformer calculator also works out the primary side at the same time.

Generator · 240V single-phase

A 20 kVA single-phase generator feeding a 240V panel: 20,000 ÷ 240 gives a full-load current of 83.33 A. Every load on that panel shares those amps, which is why the generator calculator lists standard genset sizes with their full-load amps side by side.

UPS · 208V three-phase

A 10 kVA UPS on a 208V three-phase supply: 10,000 ÷ (√3 × 208) = 10,000 ÷ 360.27 — a full-load current of 27.76 A. UPS units are rated in kVA for exactly this reason: the rating already describes the current the output can carry at its rated voltage.

When to be careful

The conversion itself is exact. The situations below are where a correct number still needs a second thought before it becomes a decision.

Balanced loads

The three-phase formulas assume the load is balanced — shared evenly across the three phases, which is how the kVA rating is defined. A heavily unbalanced load can push one phase above the figure shown here while the others sit below it. For unbalanced panels, work out each phase's single-phase current separately.

Nameplate kVA vs measured current

A nameplate kVA is a maximum rating, not a promise about what a running machine draws moment to moment. Equipment at part load draws less. If you are checking an existing circuit, a clamp meter reading is the truth; this conversion tells you what the circuit must be able to carry at full rating.

Breakers and cables need more than this number

Full-load amps is the starting point for sizing protection and conductors, not the whole job. Continuous-load rules, derating for temperature and conduit fill, and inrush current all come from the National Electrical Code and the equipment manual. Use the figure here to plan, then verify the installation against the code — or have a licensed electrician do it.

Frequently asked questions

How many amps are in 1 kVA?

It depends on the voltage and the phase, because amps = kVA × 1000 ÷ volts. At 240 V single-phase, 1 kVA is 4.17 A. At 400 V three-phase it is 1.44 A, and at 480 V three-phase it is 1.20 A. There is no single answer without a voltage — a chart that gives one without asking for volts is guessing.

How many kVA is 50 amps?

At 240 V single-phase, 50 A is 12.00 kVA. At 400 V three-phase, 50 A is 34.64 kVA, and at 480 V three-phase it is 41.57 kVA. Pick the row that matches your supply — the amps to kVA calculator runs the reverse conversion for any voltage.

What is 10 kVA in amps?

At 240 V single-phase, 10 kVA is 41.67 A. At 400 V three-phase it is 14.43 A, and at 480 V three-phase it is 12.03 A. The same 10 kVA pulls very different currents depending on the supply, which is why the voltage always comes first in this conversion.

How to calculate kVA in 3-phase?

For three-phase, amps = kVA × 1000 ÷ (√3 × line-to-line volts). Example: 100 kVA at 400 V is 100,000 ÷ (1.732 × 400) = 144.34 A. Going the other way, kVA = √3 × amps × volts ÷ 1000. If your voltage is line-to-neutral instead of line-to-line, divide by 3 × volts rather than √3 × volts.

Does power factor change a kVA to amps conversion?

No. Power factor converts kVA into kW — it separates apparent power from real power — and it never enters the kVA to amps formula, which uses only apparent power and voltage. If a calculator asks for a power factor when converting kVA to amps, it is really answering the kW question, and at a power factor of 0.8 its result will be 25% too high.

Can I convert kVA to amps for DC?

No. kVA is an AC quantity: apparent power exists because AC current and voltage alternate, and the gap between them is what power factor describes. A DC circuit is specified in watts and amps directly, where amps = watts ÷ volts. If a DC device is labelled in VA, treat that figure as watts for the current calculation.