Three-phase current

Three-Phase kVA to Amps Calculator

A dedicated three-phase converter with both voltage conventions: line-to-line (400V, 480V nameplates) and line-to-neutral (230V in a 400V system). The homepage kVA to amps calculator covers single-phase too.

Three-Phase Converter
kVA
V
Current per phase
144.34 A
100 kVA × 1000 ÷ (√3 × 400 V) = 144.34 A

Balanced three-phase load, using the line-to-line voltage on the nameplate.

15 kVA at 400V, three-phase= 21.65 A
45 kVA at 415V, three-phase= 62.60 A
100 kVA at 400V, three-phase= 144.34 A
250 kVA at 208V, three-phase= 693.93 A

The two three-phase formulas

Three-phase power can be written two equivalent ways, depending on which voltage your nameplate or meter gives you. Both describe the same physical system and must agree — if they don't, one of the voltages was read from the wrong pair of terminals.

Line-to-line
I = (kVA × 1000) ÷ (√3 × V L-L)

Use the voltage measured between any two phases — 400V, 415V, 480V, 208V. This is the voltage on almost every equipment nameplate and the default in the calculator above.

Line-to-neutral
I = (kVA × 1000) ÷ (3 × V L-N)

Use the voltage from one phase to neutral — 230V in a 400V system, 277V in a 480V system. The 3 counts the three identical phase-to-neutral contributions.

Where √3 comes from

The three phases are sine waves spaced 120° apart. Add two of them together — which is what a line-to-line measurement sees — and the peaks do not simply double: they combine to √3 (≈ 1.732) times the single-phase voltage. That is why 230 V line-to-neutral and 400 V line-to-line are the same system seen from different terminals: 230 × 1.732 ≈ 400.

Total power is the sum over three identical phases: 3 × V(L-N) × I. Rewriting with V(L-L) = √3 × V(L-N) turns that into √3 × V(L-L) × I — the form used whenever the line-to-line voltage is the known quantity. The methodology page carries the full derivation.

Line-to-line or line-to-neutral?

Check where the voltage came from. Nameplates, generator data sheets and transformer plates quote line-to-line. A multimeter reading from one phase to the neutral bar gives line-to-neutral. European 400/230V and North American 480/277V and 208/120V systems are both described by the same pair of numbers — the larger is always line-to-line.

Mixing them up is the most common three-phase error: putting 230 V into the √3 formula understates the current by a factor of √3, and putting 400 V into the 3× formula overstates it the same way. When in doubt, compute both ways with a matched pair — the answers must meet in the middle.

Worked examples

Commercial unit · 250 kVA at 208V

A 250 kVA service at 208V three-phase: 250,000 ÷ (√3 × 208) = 250,000 ÷ 360.27 — 693.93 A per phase. Low voltage and big power means serious copper: the same load at 480V would draw 300.70 A.

Workshop machine · 45 kVA at 415V

A 45 kVA machine on a 415V three-phase supply (the South Asian standard): 45,000 ÷ (√3 × 415) = 62.60 A per phase — a 80 A-class breaker territory once starting current is considered.

The same system, both ways · 100 kVA

Line-to-line: 100,000 ÷ (√3 × 400) = 144.34 A. Line-to-neutral: 100,000 ÷ (3 × 230) = 144.93 A. A whisker of difference from rounding 230.94 V down to 230 — the two formulas are the same statement.

Three-phase quick table

Per-phase amps for standard ratings at the three common line-to-line voltages. The full chart adds 120V and 240V columns and every rating in between.

kVA208V · three-phase400V · three-phase480V · three-phase
513.88 A7.22 A6.01 A
1027.76 A14.43 A12.03 A
1541.64 A21.65 A18.04 A
2569.39 A36.08 A30.07 A
50138.79 A72.17 A60.14 A
75208.18 A108.25 A90.21 A
100277.57 A144.34 A120.28 A
250693.93 A360.84 A300.70 A
5001,387.86 A721.69 A601.41 A
10002,775.72 A1,443.38 A1,202.81 A

Frequently asked questions

How do I calculate amps from kVA in three-phase?

Divide the kVA by the line-to-line voltage and by √3, in VA terms: amps = kVA × 1000 ÷ (√3 × V). Example: 100 kVA at 400 V is 100,000 ÷ (1.732 × 400) = 144.34 A per phase. That per-phase current is the figure breakers and cables are sized against.

What is 1 kVA in amps three-phase?

At 400 V three-phase, 1 kVA is 1.44 A. At 480 V it is 1.20 A, and at 208 V it is 2.78 A. Lower-voltage systems carry the same power at higher current, which is why 208 V services need heavier conductors than 480 V services of the same kVA.

Should I use 400V or 230V in the three-phase formula?

Both work, with different partners: 400 V is the line-to-line voltage and pairs with √3 (amps = kVA × 1000 ÷ (√3 × 400)); 230 V is the line-to-neutral voltage of the same system and pairs with 3 (amps = kVA × 1000 ÷ (3 × 230)). They give the same answer — 144.34 A for 100 kVA — because √3 × 400 and 3 × 230 describe the same system.

Why is there a √3 in the three-phase formula?

The three phase voltages sit 120° apart, so the voltage between any two lines is not twice the line-to-neutral voltage but √3 times it: 230 V line-to-neutral becomes 400 V line-to-line. Total power is 3 × V(L-N) × I, and substituting V(L-L) = √3 × V(L-N) gives √3 × V(L-L) × I. The √3 is geometry, not a fudge factor.

How many amps is 15 kVA three-phase?

At 400 V three-phase, 15 kVA is 21.65 A. At 480 V it is 18.04 A, and at 208 V it is 41.67 A. Watch the 208 V figure: a modest 15 kVA load already needs a 50 A-class circuit at that voltage once continuous-load rules are applied.