Current → apparent power

Amps to kVA Calculator

Turn a measured or nameplate current into apparent power. Enter the amps and the voltage — single-phase or three-phase — and get the kVA the load actually represents.

Amps → kVA Converter
A
V
Apparent power
69.28 kVA
√3 × 100 A × 400 V ÷ 1000 = 69.28 kVA

Balanced three-phase load, line-to-line voltage. Change any value and the result updates instantly.

50 A at 240V, single-phase= 12.00 kVA
100 A at 400V, three-phase= 69.28 kVA
200 A at 240V, single-phase= 48.00 kVA
63 A at 400V, three-phase= 43.65 kVA

The amps to kVA formulas

This is the kVA to amps conversion run backwards: instead of dividing apparent power by the voltage, you multiply the current by it. The √3 belongs to three-phase for the same geometric reason it appears in the forward direction.

Single-phase
kVA = (A × V) ÷ 1000

One live conductor: multiply the current by the voltage to get volt-amps, then divide by 1000 for kVA.

Three-phase · line-to-line
kVA = (√3 × A × V) ÷ 1000

The standard three-phase form, using the line-to-line voltage printed on nameplates (400V, 480V).

Three-phase · line-to-neutral
kVA = (3 × A × V) ÷ 1000

When the voltage you have is line-to-neutral — 230V in a 400V system, for example — use 3 × instead of √3 ×.

Worked examples

EV charger · 240V single-phase

A 40 A home EV charger on a 240V supply: 40 × 240 ÷ 1000 is a 9.60 kVA load. That is the number to compare against a home generator or UPS rating — not the 40 A alone.

Service entrance · 200A at 240V

A 200 A residential service at 240V single-phase carries 200 × 240 ÷ 1000 = 48.00 kVA at most. A backup generator advertised as "whole house" for that panel needs a rating in that neighbourhood before any load management.

Motor circuit · 63A at 400V three-phase

A three-phase circuit protected at 63 A on a 400V supply: √3 × 63 × 400 ÷ 1000 = 43.65 kVA. Useful when a machine's plate gives current but the supply or transformer is specified in kVA.

Amps to kVA reference table

Common breaker and circuit sizes turned into kVA at the three most asked-about voltages. Anything in between is one multiplication away in the calculator above.

Current240V · single-phase (kVA)400V · three-phase (kVA)480V · three-phase (kVA)
10 A2.406.938.31
16 A3.8411.0913.30
20 A4.8013.8616.63
32 A7.6822.1726.60
40 A9.6027.7133.26
50 A12.0034.6441.57
63 A15.1243.6552.38
80 A19.2055.4366.51
100 A24.0069.2883.14
125 A30.0086.60103.92
160 A38.40110.85133.02
200 A48.00138.56166.28

When to be careful

A clamp reading is a moment, not a rating

Current measured on a running load rises and falls with the work the load is doing. Converting a single reading gives the kVA at that moment. For sizing, use the nameplate current or the protective device's rating — the largest current the circuit is designed to carry — rather than one quiet-afternoon measurement.

Starting current is not in this conversion

Motors and compressors draw several times their running current for a moment at start. That surge matters for generator and UPS sizing, but it is not part of the amps-to-kVA identity, and no steady-state conversion can show it. Check the equipment's starting or locked-rotor figures separately.

Frequently asked questions

How many kVA is 100 amps?

At 240 V single-phase, 100 A is 24.00 kVA. At 400 V three-phase it is 69.28 kVA, and at 480 V three-phase it is 83.14 kVA. The same current means very different power on different supplies, so the voltage and phase always come first.

How do I convert amps to kVA three-phase?

Multiply the current by the line-to-line voltage and by √3, then divide by 1000: kVA = √3 × A × V ÷ 1000. Example: 63 A at 400 V is 1.732 × 63 × 400 ÷ 1000 = 43.65 kVA. If your voltage is line-to-neutral, use 3 × A × V ÷ 1000 instead.

Is amps to kVA just the reverse of kVA to amps?

Yes — both directions come from the same identity. Apparent power equals volts × amps single-phase, or √3 × volts × amps three-phase. Converting to amps divides by the voltage; converting back to kVA multiplies by it. Nothing else enters either direction.

What size generator do I need for a 100 amp load?

First turn the load into kVA at your voltage: 100 A at 240 V single-phase is 24.00 kVA, so the generator must be rated at least that — and in practice you pick the next standard size up, a 25 or 30 kVA set, so the machine is not running at its limit continuously. At 400 V three-phase the same 100 A is 69.28 kVA, a very different machine. The generator calculator lists standard sizes with their full-load amps.

Does power factor matter when converting amps to kVA?

No. Amps and kVA are linked by voltage alone (and √3 three-phase). Power factor only appears when kW enters the question — converting kVA to kW, or amps to kW. If a tool asks for a power factor to give you kVA from amps, it is mixing two different conversions.

Sources and references

The identities used here are the same standards-based formulas as the main converter, run in reverse. See the methodology page for the derivations.

Sources and references